Hager ADD210B RCBO Safety Switch 10A 1 Pole D Curve 10kA 30mA Type A 1 Module DIN Rail 230V
SKU: hagrcb11010kd
Product Image Gallery
Product Pricing
$200.81 (ex-GST)
$220.89 (inc-GST)
$220.89
$200.81
Stock and Availability
- ⚫︎ Ships in 2-5 days
Hager ADD210B 10A single-pole RCBO safety switch combining MCB and RCD protection: D-curve overcurrent, 10kA breaking, 30mA Type A earth leakage. Compact 1-module DIN rail device. AS/NZS 61009 compliant.
Electrotraders USPs
Description
Overcurrent and earth-leakage protection for high-inrush circuits.
The Hager ADD210B is a 10A single-pole RCBO (residual current breaker with overcurrent protection) combining D-curve overload and short-circuit protection with 30mA Type A earth-leakage protection in a compact 1-module DIN rail device.
Key Features
- Rated current: 10A, single pole (1P)
- D tripping curve (10–20x In) for high-inrush loads
- 10kA breaking capacity (Icn) to IEC 60898-1
- 30mA residual current, Type A (detects AC and pulsating DC)
- Rated voltage 230–240V AC; insulation voltage 250V
- Compact 1-module width (17.8mm) DIN rail mount
- Accepts conductors 1–25mm² rigid, 1–16mm² flexible
- IP20; rated impulse withstand 4000V
Buy online now – fast dispatch on Hager safety switches Australia-wide.
Why it Matters
Two protections in a single device.
The ADD210B is an RCBO – a residual current breaker with overcurrent protection – combining the functions of an MCB and an RCD in one module. It protects a circuit against overload and short circuit and, at the same time, disconnects on an earth-leakage fault of 30mA or more, guarding against electric shock. Combining both roles in one 1-module device saves board space compared with separate MCB and RCD components.
D curve and Type A leakage detection.
The D tripping characteristic trips on short circuit at 10 to 20 times rated current, suited to circuits with high inrush – transformers, motors and switch-mode supplies – that would nuisance-trip a standard C-curve device. Its Type A residual sensing detects both AC and pulsating DC earth-leakage currents, covering modern electronic loads, and its 10kA breaking capacity handles the fault levels found in commercial and industrial switchboards.
Built for Australian switchboards.
At one module (17.8mm) wide, 115mm high and 70mm deep, the ADD210B clips onto standard 35mm DIN rail. Terminals take rigid conductors up to 25mm², and it is rated IP20 with a 4kV impulse withstand. It complies with AS/NZS 61009 for RCBOs and suits residential, commercial and industrial final circuits with high-inrush loads requiring combined overcurrent and earth-leakage protection.
Q: What is an RCBO and how is the ADD210B different from an MCB?
An RCBO combines an MCB and an RCD in one device: it protects against overload and short circuit like an MCB, and also trips on earth leakage (30mA here) to guard against electric shock – protection a plain MCB does not provide.
Q: What does the D curve mean on the ADD210B?
The D curve trips on short circuit at 10 to 20 times the rated current, suited to high-inrush loads such as transformers and motors that would nuisance-trip a lower B or C curve.
Q: What does Type A mean on the ADD210B?
Type A residual current detection responds to both AC and pulsating DC earth-leakage currents, covering electronic loads that a basic Type AC device may not detect.
(hagrcb11010kd)
Specifications
| Architecture | |
| Type of pole | 1P |
| Curve | D |
| Electric current | |
| Rated current | 10 A |
| Rated residual operating current Idn | 30 mA |
| Rated current -25DegC | 13,30 A |
| Rated current at -20DegC | 13 A |
| Rated current -15DegC | 12,70 A |
| Rated current -10DegC | 12,40 A |
| Rated current -5DegC | 12,10 A |
| Rated current at 0DegC | 11,80 A |
| Rated current 5DegC | 11,50 A |
| Rated current 10DegC | 11,20 A |
| Rated current 15DegC | 10,90 A |
| Rated current at 20DegC | 10,60 A |
| Rated current 25DegC | 10,30 A |
| Rated current 30DegC | 10 A |
| Rated current 35DegC | 9,75 A |
| Rated current at 40DegC | 9,50 A |
| Rated current at 50DegC | 9 A |
| Rated current 55DegC | 8,75 A |
| Rated current 60DegC | 8,50 A |
| Min./max. threshold value of the AC thermal operation | 1,13 - 1,45 A |
| Safety | |
| Residual current type | A |
| Ingress Protection (IP) class | IP20 |
| Main electrical attributes | |
| Rated short-circuit breaking capacity Icn AC according to IEC 60898-1 | 10 kA |
| Voltage | |
| Rated insulation voltage Ui | 250 V |
| Rated impulse withstand voltage Uimp | 4000 V |
| Rated operational voltage Ue | 230 - 240 V |
| Overvoltage category according to IEC 60947-1 | 3 |
| Power | |
| Total power loss under IN | 2,80 W |
| Frequency | |
| Frequency | 50 - 60 Hz |
| Use conditions | |
| Max. Altitude | 2000 m |
| Operating temperature | -5 - 40 DegC |
| Storage/transport temperature | -40 - 70 DegC |
| Endurance | |
| Electric endurance in number of cycles | 2000 |
| Number of mechanical operations | 10000 |
| Connection | |
| Cross-section of input with screws, for flexible conductors | 1 - 10 mm^2 |
| Cross-section of input with screws, for massive conductors | 1 - 16 mm^2 |
| Cross-section of input and output with screws, for flexible conductors | 1 - 16 mm^2 |
| Cross-section of input and output with screws, for massive conductors | 1 - 25 mm^2 |
| Installation, mounting | |
| Type of top connection for modular devices | Screw terminal |
| Type of bottom connection for modular devices | biconnect |
| Capacity | |
| Number of modules | 1 |
| Dimensions | |
| Height | 115 mm |
| Width | 17,80 mm |
| Depth | 70 mm |
| Compatibility | |
| Suitable for DIN Rail | Yes |
| SKU | hagrcb11010kd |
| Manfacturer Part Number | ADD210B |
| Barcode # | 3250611036012 |
| Brand | Hager |