Hager CDA440T RCCB Safety Switch 40A 4 Pole (3P+N) 30mA Type A 230/400V AC 4 Module IP20 DIN Rail
SKU: hagrcd440
Product Image Gallery
Product Pricing
$40.00 (ex-GST)
$44.00 (inc-GST)
$44.00
$40.00
Bulk Carton size
36Stock and Availability
- ⚫︎ Only 1 Left!
Hager CDA440T residual current circuit breaker: 4 pole (3P+N), 40A, 30mA Type A sensing for AC and pulsating DC earth faults. 230/400V AC, 440V max, 6kA conditional short-circuit rating, 4 modules, IP20. Earth leakage protection only, no overcurrent.
Electrotraders USPs
Description
Four-pole earth leakage protection for 400V boards.
The Hager CDA440T is a 40A residual current circuit breaker with 30mA Type A sensing across three phases and neutral. It disconnects the circuit when leakage to earth reaches its trip threshold, covering both AC and pulsating DC residual currents in a 4 module DIN rail body.
Key Features
- 4 pole (3P+N), 40A rated current
- 30mA rated residual operating current
- Type A sensing: AC and pulsating DC residual currents
- 230/400V AC, 50Hz, 440V maximum operating voltage
- 6kA conditional short-circuit current (Inc) to EN 61008-1
- 1.5kA breaking and opening capacity (Idm)
- 4 modules: 70mm wide, 83mm high, 70mm deep
- Screw top terminals, biconnect bottom, 2.8Nm torque
- IP20, 6.5W power loss at rated current
- 2,000 electrical cycles, 4,000 mechanical operations
Buy online today – quick dispatch from our Australian warehouse.
Specifying the CDA440T in a Three-Phase Board
An RCCB is not a circuit breaker
This is an important distinction at ordering time. An RCCB provides residual current (earth leakage) protection only. It does not protect cabling against overload or short-circuit, so upstream or downstream overcurrent protection is still required. Hager's 6kA figure is a conditional short-circuit rating, meaning the device withstands that level of fault when backed by a suitable protective device. If you want both functions in one unit, an RCBO such as the Hager ADM series is the alternative.
Why Type A sensing
A Type AC device only responds to sinusoidal AC residual currents. Type A extends that to pulsating DC residual currents, which arise from equipment containing rectifiers and electronic power supplies. Hager classifies the CDA440T as Type A, Class A.
Installation data
- Terminals accept 1-25mm² rigid or 1-16mm² flexible conductors, top and bottom torqued to 2.8Nm.
- Insulation voltage 500V with a 4kV impulse withstand rating.
- Rated for installation up to 2000m altitude.
- IP20 means it belongs inside an enclosed switchboard, not in an exposed position.
- Optional Hager accessories include a shunt trip, undervoltage release, padlockable locking kit and heat dissipation insert.
- Installation must be carried out by a licensed electrician to AS/NZS 3000.
Q: Does the Hager CDA440T protect against overload and short-circuit?
A: No. It is an RCCB, so it provides earth leakage protection only. Separate overcurrent protection is required, and its 6kA rating is a conditional short-circuit figure that assumes a suitable upstream device.
Q: What does Type A mean on the Hager CDA440T?
A: Type A residual current sensing detects both AC and pulsating DC earth fault currents, unlike Type AC devices which detect AC residual currents only.
Q: How wide is the Hager CDA440T in a switchboard?
A: It takes 4 DIN rail modules, measuring 70mm wide by 83mm high and 70mm deep.
(hagrcd440)
Specifications
| Product Identity | |
| Brand | Hager |
| Model / Part Number | CDA440T |
| Product Type | Residual Current Circuit Breaker (RCCB) |
| Barcode (EAN) | 3250611615507 |
| Electrical Ratings | |
| Number of Poles | 4-pole (3P+N) |
| Rated Current (In) | 40A |
| Rated Residual Operating Current (IΔn) | 30mA |
| Residual Current Type | Type A (AC and pulsating DC) |
| Rated Operational Voltage (Ue) | 230/400V AC |
| Maximum Operating Voltage | 440V AC |
| Rated Insulation Voltage (Ui) | 500V |
| Rated Impulse Withstand Voltage (Uimp) | 4,000V (4kV) |
| Frequency | 50Hz |
| Conditional Short-Circuit Current (Inc) | 6kA (per EN 61008-1, with suitable upstream MCB) |
| Rated Breaking Capacity (Idm) | 1.50kA |
| Total Power Loss at Rated Current | 6.50W |
| Temperature Performance (No Derating) | |
| Rated Ambient Temperature Range | -25°C to +70°C |
| Rated Current Across Full Range | 40A (no derating at any temperature in range) |
| Physical Characteristics | |
| Width | 70mm (4 DIN modules) |
| Height | 83mm |
| Depth | 70mm |
| Mounting | 35mm DIN rail (symmetrical / type O) |
| Neutral Position | Right |
| Maximum Installation Altitude | 2,000m |
| Terminals & Wiring | |
| Top Terminals | Screw type (aligned) |
| Bottom Terminals | Biconnect (screw, aligned) |
| Max Conductor — Rigid | 1–25mm² |
| Max Conductor — Flexible | 1–16mm² |
| Terminal Tightening Torque (Top & Bottom) | 2.8Nm |
| Endurance & Protection | |
| Electrical Endurance | 2,000 operations |
| Mechanical Endurance | 4,000 operations |
| Ingress Protection (IP) | IP20 |
| Standards & Compliance | |
| Standard | EN 61008-1 |
| Australian Installation Standard | AS/NZS 3000 |
| RoHS Compliance | Yes |
| REACh Declaration | Available from Hager |
| Warranty | |
| Manufacturer Warranty | 2 years (domestic and commercial) |
| SKU | hagrcd440 |
| Manfacturer Part Number | CDA440T |
| Barcode # | 3.25061E+12 |
| Brand | Hager |
| Assembled Length | 0.070m |
| Assembled Height | 0.083m |
| Assembled Width | 0.070m |
Shipping Calculator
You May Also Like
Others Also Bought
More From This Category