Hager ADM410T combined RCBO safety switch: 10A C curve overload and short-circuit protection with 30mA Type A residual current detection across all four poles in one 4 module (71mm) DIN rail unit. For 3 phase (3P+N) circuits, 6kA breaking, IP2X, AS/NZS 61
Electrotraders USPs
Description
The Hager ADM410T is a 10A 4 Pole (3 phase plus neutral) RCBO that combines overload protection, short-circuit protection and 30mA earth leakage detection for three-phase circuits in a single 4 module DIN rail device.
Built to AS/NZS 61009, this four-pole RCBO unites a C curve miniature circuit breaker with a Type A residual current device so one unit protects a three-phase circuit against overcurrent faults and protects people against electric shock. It is designed for 3 phase (3P+N) final subcircuits and control equipment such as three-phase motors, pumps, HVAC plant and machinery. The Type A residual current element responds to both AC and pulsating DC leakage currents, giving broader coverage than a basic Type AC device as more equipment uses electronic drives and rectified supplies.
- 10A rated current, C curve tripping characteristic
- 4 Pole (3P+N) configuration, all four poles protected and switched
- 30mA rated residual operating current, Type A
- 6kA rated short-circuit breaking capacity (Icn) to IEC 61009-1
- Combined MCB and RCD protection in one device
- 4 module width (71mm) on 35mm DIN rail
- 230-415V rated operational voltage (three phase)
- Rated insulation voltage Ui 500V, impulse withstand Uimp 4kV
- Test button for periodic RCD verification
- Screw terminals top, biconnect bypass bottom for busbar wiring
- IP2X ingress protection with earth fault indication
- Operating temperature -25°C to +40°C
Order yours online now and Electrotraders will dispatch your genuine Hager ADM410T within 24 hours.
Why choose the Hager ADM410T?
A four-pole RCBO delivers both circuit-breaker and safety-switch functions for a complete three-phase circuit in one device, breaking all three phases and the neutral together on a fault. Providing RCD protection at the individual circuit level means an earth leakage fault on one three-phase circuit does not trip other circuits sharing an upstream device. The 10A rating and C curve suit three-phase control and light-load applications, while the 6kA breaking capacity is appropriate for typical commercial and industrial distribution boards.
What is a Type A RCBO?
A Type A residual current device detects sinusoidal AC earth leakage as well as pulsating DC leakage produced by equipment with rectifiers and electronic controls. This broader coverage is increasingly specified for modern three-phase installations that run variable-speed drives and electronic loads. The ADM410T trips on residual currents at its rated 30mA sensitivity, the level associated with personal protection against electric shock.
Installation and wiring
The ADM410T mounts on standard 35mm DIN rail and occupies 4 modules (71mm) of board width. Terminals accept 1-25mm² rigid or 1-16mm² flexible conductors at a nominal tightening torque of 2Nm. The biconnect bypass bottom connection accepts pin-type busbar for combing devices in a three-phase distribution board, and the device supports 360° mounting orientation. All work must be carried out by a licensed electrician in accordance with AS/NZS 3000.
Frequently asked questions
Is the Hager ADM410T suitable for three-phase circuits?
Yes. It is a 4 Pole (3P+N) RCBO designed to protect a three-phase plus neutral circuit, switching and protecting all four poles together.
Does it provide both overload and earth leakage protection?
Yes. It is a combined RCBO, so a single device provides C curve overload and short-circuit protection plus 30mA Type A residual current (earth leakage) protection.
How much board space does the ADM410T occupy?
It is a 4 module device, 71mm wide, mounting on standard 35mm DIN rail.
(hagrcb410)
Specifications
| Electric current | |
| Rated current | 10 A |
| Rated residual operating current Idn | 30 mA |
| Rated current -25DegC | 12,30 A |
| Rated current at -20DegC | 12,10 A |
| Rated current -15DegC | 11,90 A |
| Rated current -10DegC | 11,70 A |
| Rated current -5DegC | 11,50 A |
| Rated current at 0DegC | 11,30 A |
| Rated current 5DegC | 11,10 A |
| Rated current 10DegC | 10,90 A |
| Rated current 15DegC | 10,70 A |
| Rated current at 20DegC | 10,50 A |
| Rated current 25DegC | 10,20 A |
| Rated current 30DegC | 10 A |
| Rated current 35DegC | 9,80 A |
| Rated current at 40DegC | 9,50 A |
| Rated current at 45DegC | 9,20 A |
| Rated current at 50DegC | 9 A |
| Rated current 55DegC | 8,70 A |
| Rated current 60DegC | 8,40 A |
| Rated short-circuit breaking capacity Icn under 230 V AC according to IEC 61009-1 | 6 kA |
| Architecture | |
| Curve | C |
| Neutral position | Right |
| Type of pole | 4P |
| Number of protected poles | 4 |
| Capacity | |
| Number of modules | 4 |
| Safety | |
| Residual current type | A |
| Ingress Protection (IP) class | IP2X |
| Voltage | |
| Type voltage supply | AC |
| Rated operational voltage Ue | 230 - 415 V |
| Rated insulation voltage Ui | 500 V |
| Dielectric strength value of power frequency | 2 kV |
| Rated impulse withstand voltage Uimp | 4000 V |
| Overvoltage category according to IEC 60947-1 | 3 |
| Installation, mounting | |
| Nominal tightening torque top terminal | 2 - 2 Nm |
| Nominal tightening torque down terminal | 2 - 2 Nm |
| Nominal tightening torque | 2 - 2 Nm |
| 360?ø mounting position possible | Yes |
| Type of top connection for modular devices | Screw terminal |
| Type of bottom connection for modular devices | biconnect, Bypass |
| Main electrical attributes | |
| Rated short-circuit breaking capacity Icn AC according to IEC 60898-1 | 6 kA |
| Frequency | |
| Frequency | 50 - 50 Hz |
| Connection | |
| Cross-section of input with screws, for flexible conductors | 1 - 16 mm^2 |
| Cross-section of input with screws, for massive conductors | 1 - 25 mm^2 |
| Use conditions | |
| Class of energy limitation I^2t | 3 |
| Operating temperature | -25 - 40 DegC |
| Dimensions | |
| Height | 84 mm |
| Width | 71 mm |
| Depth | 70 mm |
| Power | |
| Total power loss under IN | 9,70 W |
| SKU | hagrcb410 |