Hager ADC925T 25 Amps 1 Pole plus Neutral RCBO Safety Switch 6kA 30mA Type A C Curve 1 Module DIN Rail
SKU: hagrcb1256k
Product Image Gallery
Product Pricing
$40.00 (ex-GST)
$44.00 (inc-GST)
$44.00
$40.00
Stock and Availability
- ⚫︎ Only 1 Left!
Hager ADC925T 1P+N RCBO in a slimline 17.7 mm DIN module. 25 A C curve, 30 mA Type A earth leakage sensing and 6 kA breaking capacity on 230-240 V circuits. Non-sensitive line and load terminals, IP2X, IEC 60898-1. In stock, ships in 24 hours.
Electrotraders USPs
Description
Full 1P+N protection in a single slim module.
The Hager ADC925T switches and protects both active and neutral, yet occupies just one 17.7 mm module of DIN rail. It frees up board space where a conventional two-module 1P+N device would not fit, without dropping neutral switching.
Key Features
- Hager ADC925T RCBO, 1 pole plus neutral, 1 module (17.7 mm) wide
- 25 A rated current, C curve tripping characteristic
- 30 mA rated residual operating current, Type A
- 6 kA rated short circuit breaking capacity (Icn, IEC 60898-1)
- 230 - 240 V AC rated operational voltage, 50 - 60 Hz
- Non-sensitive line and load terminals - no rewiring when replacing another brand
- Rated insulation voltage 440 V, impulse withstand 4 kV, energy limitation class 3
- Screw terminal top, BIconnect bottom connection
- Accepts 1 - 16 mm² solid or 1 - 10 mm² flexible conductors
- Mounts on 35 mm DIN rail, IP2X rated
- 20,000 mechanical operations, 10,000 electrical cycles
- Manufactured to IEC 60898-1, RoHS conform
Add to cart - in stock and dispatched Australia-wide within 24 hours.
Neutral Switching, One Module
The ADC925T is a true 1P+N device: it switches and protects both the active and the neutral conductor. Traditionally that meant a two-module unit. This slimline design does it in a single 17.7 mm module, height 85 mm and depth 70 mm, freeing rail space in domestic switchboards and load centres and leaving more room for wiring inside the enclosure.
Fast Retrofit, No Rewiring
Both the line and load terminals are non-sensitive, so the device works regardless of supply orientation. When replacing an RCBO from another brand you can reuse the existing wiring rather than swapping active and neutral, which cuts fault-finding and install time on site.
Type A Earth Leakage Sensing
As a Type A RCBO the ADC925T detects both sinusoidal AC earth leakage and pulsating DC earth leakage, unlike Type AC which detects only the AC component. With switch mode power supplies, inverters and variable speed drives now common on Australian final circuits, Type A is the practical baseline for personal and fire protection. It trips at a rated residual current of 30 mA.
Rated for Australian Conditions
Rated operational voltage is 230 - 240 V at 50 - 60 Hz, matching the Australian supply, with a maximum operating voltage of 264 V. Hager publishes a full derating curve: 25 A at 30 °C ambient, 23.70 A at 40 °C and 21 A at 60 °C, relevant where meter boxes and plant rooms run hot. The device is rated to 2000 m altitude.
Q: Is the Hager ADC925T single pole or double pole?
A: It is a 1 pole plus neutral (1P+N) device that switches and protects both the active and neutral conductors, in a single 17.7 mm module. The single-pole ADC220 range protects the active only.
Q: Do I need to rewire when replacing another brand with the ADC925T?
A: No. The line and load terminals are non-sensitive, so the device operates regardless of which way the supply is connected. In most cases the existing wiring can be reused.
Q: What is the difference between the ADC925T and the ADD925T?
A: Both are 25A 1P+N 6kA 30mA Type A RCBOs. The ADC925T has a C curve for general circuits, while the ADD925T has a D curve for high-inrush loads such as motors and transformers.
(hagrcb1256k)
Specifications
| Architecture | |
| Type of pole | 1P+N |
| Curve | C |
| Electric current | |
| Rated current | 25 A |
| Rated residual operating current Idn | 30 mA |
| Rated current -25DegC | 32,40 A |
| Rated current at -20DegC | 31,70 A |
| Rated current -15DegC | 31,10 A |
| Rated current -10DegC | 30,40 A |
| Rated current -5DegC | 29,70 A |
| Rated current at 0DegC | 29 A |
| Rated current 5DegC | 28,40 A |
| Rated current 10DegC | 27,70 A |
| Rated current 15DegC | 27 A |
| Rated current at 20DegC | 26,30 A |
| Rated current 25DegC | 25,70 A |
| Rated current 30DegC | 25 A |
| Rated current 35DegC | 24,30 A |
| Rated current at 40DegC | 23,70 A |
| Rated current at 50DegC | 22,30 A |
| Rated current 55DegC | 21,60 A |
| Rated current 60DegC | 21 A |
| Min./max. threshold value of the AC thermal operation | 1,13 - 1,45 A |
| Safety | |
| Residual current type | A |
| Ingress Protection (IP) class | IP2X |
| Main electrical attributes | |
| Rated short-circuit breaking capacity Icn AC according to IEC 60898-1 | 6 kA |
| Voltage | |
| Rated insulation voltage Ui | 440 V |
| Rated impulse withstand voltage Uimp | 4000 V |
| Max. operating voltage | 264 V |
| Rated operational voltage Ue | 230 - 240 V |
| Overvoltage category according to IEC 60947-1 | 3 |
| Power | |
| Total power loss under IN | 11,38 W |
| Frequency | |
| Frequency | 50 - 50 Hz |
| Use conditions | |
| Max. Altitude | 2000 m |
| Class of energy limitation I^2t | 3 |
| Operating temperature | -25 - 70 DegC |
| Storage/transport temperature | -25 - 80 DegC |
| Endurance | |
| Electric endurance in number of cycles | 10000 |
| Number of mechanical operations | 20000 |
| Connection | |
| Cross-section of input with screws, for flexible conductors | 1 - 10 mm^2 |
| Cross-section of input with screws, for massive conductors | 1 - 16 mm^2 |
| Cross-section of input and output with screws, for flexible conductors | 1 - 10 mm^2 |
| Cross-section of input and output with screws, for massive conductors | 1 - 16 mm^2 |
| Installation, mounting | |
| Type of top connection for modular devices | Screw terminal |
| Type of bottom connection for modular devices | biconnect |
| Capacity | |
| Number of modules | 1 |
| Dimensions | |
| Height | 85 mm |
| Width | 17,70 mm |
| Depth | 70 mm |
| Compatibility | |
| Suitable for DIN Rail | Yes |
| SKU | hagrcb1256k |
| Manfacturer Part Number | ADC925T |
| Barcode # | 3250611033370 |
| Brand | Hager |
Shipping Calculator