Hager NT110C 10A single-pole miniature circuit breaker (MCB) with C tripping curve and 10kA breaking capacity. Compact 1-module DIN rail design protects circuits against overload and short circuit. AS/NZS 60898 compliant.

Electrotraders USPs

Fast Shipping, Trusted by Government, Easy Returns, Free Shipping over $200


Description

10A protection with 10kA breaking.

The Hager NT110C is a 10A single-pole miniature circuit breaker (MCB) with a C tripping curve and 10kA breaking capacity, protecting circuits against overload and short circuit from a compact 1-module DIN rail body.

Key Features

  • Rated current: 10A, single pole (1P)
  • C tripping curve (5–10x In)
  • 10kA breaking capacity (Icn) to IEC 60898-1
  • Rated voltage 240–415V AC, insulation voltage 500V
  • Compact 1-module width (17.5mm) DIN rail mount
  • Accepts conductors 1–35mm² rigid, 1–25mm² flexible
  • Energy limiting class 3; IP20; 360° mounting
  • Compliant with AS/NZS 60898.1

View specs and order online – fast dispatch on Hager circuit protection Australia-wide.

 

Why it Matters

A staple sub-circuit breaker.
The NT110C is a 10A miniature circuit breaker, protecting a circuit against both overload and short circuit and tripping automatically when either occurs. A 10A rating is a common size for lighting circuits and small power sub-circuits, and its high 10kA breaking capacity handles the fault levels found in commercial and industrial switchboards, making it a versatile choice across a wide range of boards.

C curve for general-purpose loads.
The C tripping characteristic trips on short circuit at 5 to 10 times rated current, the general-purpose curve suited to mixed resistive and moderately inductive loads. Backed by a 10kA short-circuit breaking capacity to IEC 60898-1 and energy limiting class 3, the NT110C limits let-through energy during a fault to help protect downstream cabling and equipment.

Built for Australian switchboards.
At one module (17.5mm) wide, 83mm high and 70mm deep, the NT110C clips onto standard 35mm DIN rail with 360° mounting flexibility, and its terminals take rigid conductors up to 35mm² at 2.8Nm. It is compliant with AS/NZS 60898.1, rated IP20, and operates from -25°C to 70°C to suit meter boxes, distribution boards and plant rooms across Australian conditions. Hager auxiliaries including the MZ201 auxiliary contact, MZ202 alarm contact and MZ203/MZ204 shunt trips are available.

Q: What is the Hager NT110C used for?
It is a 10A single-pole MCB for protecting lighting and small power sub-circuits against overload and short circuit, with a 10kA rating suited to commercial and industrial boards.

Q: What does the C curve mean on the NT110C?
The C curve trips on short circuit at 5 to 10 times the rated current, making it the general-purpose characteristic for mixed resistive and moderately inductive loads.

Q: What is the difference between the NT110C (10kA) and a 6kA MCB?
10kA is the rated short-circuit breaking capacity, suited to higher-fault commercial and industrial boards; a 6kA breaker such as Hager's MSN range is used where fault levels are lower, typically residential and light commercial.

(hagmcb11010k)

Specifications

Electric current
Rated current 10 A
Rated short-circuit breaking capacity Icn under 230 V AC according to IEC 60898-1 10 kA
Architecture
Type of pole 1P
Curve C
Capacity
Number of modules 1
Installation, mounting
Nominal tightening torque top terminal 2,80 - 2,80 Nm
Nominal tightening torque down terminal 2,80 - 2,80 Nm
Nominal tightening torque 2,80 - 2,80 Nm
Type of bottom connection for modular devices biconnect
Type of top connection for modular devices Screw terminal
360?ø mounting position possible Yes
Main electrical attributes
Rated short-circuit breaking capacity Icn AC according to IEC 60898-1 10 kA
Voltage
Rated operational voltage Ue 240 - 415 V
Type voltage supply AC
Rated insulation voltage Ui 500 V
Rated impulse withstand voltage Uimp 4000 V
Frequency
Frequency 50 - 60 Hz
Safety
Ingress Protection (IP) class IP20
Use conditions
Degree of pollution according to IEC 60664 / IEC 60947-2 2
Class of energy limitation I^2t 3
Air humidity protection For all climates
Operating temperature -25 - 70 DegC
Power
Total power loss under IN 1,80 W
Connectivity
Type of connection Screw terminal
Top connection alignment for modular devices Aligned terminal
Down connection alignment for modular devices Aligned terminal
Dimensions
Height 83 mm
Width 17,50 mm
Depth 70 mm
Connection
Cross-section of input and output with screws, for massive conductors 1 - 35 mm^2
Cross-section of input and output with screws, for flexible conductors 1 - 25 mm^2
Cross-section of input with screws, for flexible conductors 1 - 25 mm^2
Cross-section of input with screws, for massive conductors 1 - 35 mm^2
SKU hagmcb11010k
Manfacturer Part Number NT110C
Barcode # 3250614807015
Brand Hager