Hager NT140C Miniature Circuit Breaker MCB 40A 1 Pole C Curve 10kA 1 Module DIN Rail 240-415V

SKU: hagmcb14010k

Product Image Gallery

Product image thumbnail for SKU hagmcb14010k

Product Pricing

$12.81 (ex-GST)

$14.09 (inc-GST)

$14.09

$12.81

(inc-GST)
(ex-GST)

Stock and Availability

  • ⚫︎ Ships in 24 hours

Hager NT140C 40A single-pole miniature circuit breaker (MCB) with C tripping curve and 10kA breaking capacity. Compact 1-module DIN rail design protects circuits against overload and short circuit. AS/NZS 60898 compliant.

Electrotraders USPs

Fast Shipping, Trusted by Government, Easy Returns, Free Shipping over $200


Description

40A protection with 10kA breaking.

The Hager NT140C is a 40A single-pole miniature circuit breaker (MCB) with a C tripping curve and 10kA breaking capacity, protecting circuits against overload and short circuit from a compact 1-module DIN rail body.

Key Features

  • Rated current: 40A, single pole (1P)
  • C tripping curve (5–10x In)
  • 10kA breaking capacity (Icn) to IEC 60898-1
  • Rated voltage 240–415V AC, insulation voltage 500V
  • Compact 1-module width (17.5mm) DIN rail mount
  • Accepts conductors 1–35mm² rigid, 1–25mm² flexible
  • Energy limiting class 3; IP20; 360° mounting
  • Compliant with AS/NZS 60898.1

Buy online now – fast dispatch on Hager circuit protection Australia-wide.

 

Why it Matters

For sub-mains and heavy circuits.
The NT140C is a 40A miniature circuit breaker, protecting a circuit against both overload and short circuit and tripping automatically when either occurs. A 40A rating suits sub-mains and the heaviest single final circuits – large appliances, sub-boards and high-demand equipment feeds – and its high 10kA breaking capacity handles the fault levels found in commercial and industrial switchboards.

C curve for general-purpose loads.
The C tripping characteristic trips on short circuit at 5 to 10 times rated current, the general-purpose curve suited to mixed resistive and moderately inductive loads. Backed by a 10kA short-circuit breaking capacity to IEC 60898-1 and energy limiting class 3, the NT140C limits let-through energy during a fault to help protect downstream cabling and equipment.

Built for Australian switchboards.
At one module (17.5mm) wide, 83mm high and 70mm deep, the NT140C clips onto standard 35mm DIN rail with 360° mounting flexibility, and its terminals take rigid conductors up to 35mm² at 2.8Nm. It is compliant with AS/NZS 60898.1, rated IP20, and operates from -25°C to 70°C to suit meter boxes, distribution boards and plant rooms across Australian conditions. Hager auxiliaries including the MZ201 auxiliary contact, MZ202 alarm contact and MZ203/MZ204 shunt trips are available.

Q: What is the Hager NT140C used for?
It is a 40A single-pole MCB for protecting sub-mains and heavy single circuits – such as sub-boards and large appliance feeds – against overload and short circuit, with a 10kA rating suited to commercial and industrial boards.

Q: What does the C curve mean on the NT140C?
The C curve trips on short circuit at 5 to 10 times the rated current, making it the general-purpose characteristic for mixed resistive and moderately inductive loads.

Q: What is the difference between the NT140C (10kA) and a 6kA MCB?
10kA is the rated short-circuit breaking capacity, suited to higher-fault commercial and industrial boards; a 6kA breaker such as Hager's MSN range is used where fault levels are lower, typically residential and light commercial.

(hagmcb14010k)

Specifications

Electric current
Rated current40 A
Rated short-circuit breaking capacity Icn under 230 V AC according to IEC 60898-110 kA
Architecture
Type of pole1P
CurveC
Capacity
Number of modules1
Installation, mounting
Nominal tightening torque top terminal2,80 - 2,80 Nm
Nominal tightening torque down terminal2,80 - 2,80 Nm
Nominal tightening torque2,80 - 2,80 Nm
Type of bottom connection for modular devicesbiconnect
Type of top connection for modular devicesScrew terminal
360?ø mounting position possibleYes
Main electrical attributes
Rated short-circuit breaking capacity Icn AC according to IEC 60898-110 kA
Voltage
Rated operational voltage Ue240 - 415 V
Type voltage supplyAC
Rated insulation voltage Ui500 V
Rated impulse withstand voltage Uimp4000 V
Frequency
Frequency50 - 60 Hz
Safety
Ingress Protection (IP) classIP20
Use conditions
Degree of pollution according to IEC 60664 / IEC 60947-22
Class of energy limitation I^2t3
Air humidity protectionFor all climates
Operating temperature-25 - 70 DegC
Power
Total power loss under IN4,80 W
Connectivity
Type of connectionScrew terminal
Top connection alignment for modular devicesAligned terminal
Down connection alignment for modular devicesAligned terminal
Dimensions
Height83 mm
Width17,50 mm
Depth70 mm
Connection
Cross-section of input and output with screws, for massive conductors1 - 35 mm^2
Cross-section of input and output with screws, for flexible conductors1 - 25 mm^2
Cross-section of input with screws, for flexible conductors1 - 25 mm^2
Cross-section of input with screws, for massive conductors1 - 35 mm^2
SKU hagmcb14010k
Manfacturer Part Number NT140C
Barcode # 3250614807060
Brand Hager

Shipping Calculator